Display Message Meaning Corrective Action
Static Bypass Switch Module
Removed
The system no longer detects a static
bypass switch module.
Option 1: Ensure that the static
bypass switch module is installed
properly.
Option 2: Call Schneider Electric
Customer Support for replacement
of the static bypass switch module.
System in Maintenance Bypass The system is in maintenance
bypass: the Q2 breaker is open and
the Q3 breaker is closed.
No corrective action necessary.
System Power Supply Card Fault The system power supply card has
failed and requires replacement.
Ensure that the power supply card is
installed properly. See “Replace a
Power Management Card“.
System Start-Up Conguration Fault The system conguration download
has failed. Unable to determine the
system voltage or frame size.
Check for other alarms and contact
Schneider Electric Customer
Support (see the back cover).
Technical check recommended Regular maintenance requirements
and the end of service life
consumable components.
Contact Schneider Electric Customer
Support (see the back cover).
Warranty expiring soon The end of the contractual legal
warranty.
Contact Schneider Electric Customer
Support (see the back cover).
990–3015E-001
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation