Conguration
System Settings
Set Up the Network
1. Select Admin and press ENTER.
UPS Alarms
Power Dist Log
Switch Gear → Admin
Environment Help
2. Select Network Setup and press ENTER.
→ Network Setup
Local Interface
Date/Time
Device ID
3. Select Mode and press ENTER.
Stat:
Mode:
IP:
SM:
4. Select Fixed IP Addr to give a specic IP
address to the UPS system or select one of the
other three methods to obtain an IP address. In
this example Fixed IP Addr mode is selected.
Fixed IP Addr
DHCP Only
BOOTP Only
DHCP & BOOTP
5. Select IP (Internet Protocol), SM (Subnet
Mask), and GW (GateWay) and change the
settings using the UP and DOWN arrow keys.
Press ENTER to conrm the changes.
IP:
SM:
GW:
20
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
990–3015E-001