8. Select Turn UPS On into Bypass and press
ENTER.
Turn UPS On
→ UPS On into Bypass
9. Select Continue Turn On and press ENTER.
Battery back-up not
available in bypass!
>Cancel
→ >Continue Turn On
10. Conrm by selecting Yes, On Into Bypass
and press ENTER.
Confirm:
UPS on Into Bypass
>NO, ABORT
→ >Yes, On Into Bypass
11. Wait for the UPS to turn the load on.
Turning UPS on Into
Bypass.
Please wait...
12. The UPS is now ON.
Note: The H2 LED next to the Q2
switch will turn on, indicating that it
is safe to operate the Q2 switch.
UPS’s output is now
in bypass
Press any key...
13. Set the Q2 switch on the PDU, PDU-XR or
the external maintenance bypass panel to the
ON position.
Note: The H3 LED next to the Q3
switch will turn on, indicating that it
is safe to operate the Q3 switch.
14. Set the Q3 switch to the OFF position.
15. Use the display interface to transfer the UPS
out of bypass:
16. Select UPS and press ENTER.
→ UPS Alarms
Power Dist Log
Switch Gear Admin
Environment Help
17. Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
990–3015E-001
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
17