Perform a Total Power Off
WARNING: This procedure will disconnect the load.
Note: If shutdown via the display is disabled, then you cannot perform this procedure and
the message: Command not allowed, UPS congured to never shutdown appears. If
you want to enable shutdown via the display, this is done by a Field Service Engineer via
the UPSTuner.
1. Select UPS and press ENTER.
→ UPS Alarm
Power Dist Log
Switch Gear Admin
Environment Help
2. Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
3. Select Turn UPS Off and press ENTER.
→ Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
4. Select No, Don’t Notify to shut down without
delay and press ENTER.
Note: This action will cut all power
to the load without shutting it down
rst. If you want to shut down the
servers rst, then choose Yes, Notify
Servers. Note that this function
is only available for servers with
PowerChute.
Notify PowerChute ?
Cancel
Yes, Notify Servers
→ No, Don't Notify
5. Conrm YES, Turn UPS Off and press
ENTER.
Turn UPS off
Without Server
Notification?
> NO, ABORT
→> YES, Turn UPS Off
6. Wait for the UPS to turn off.
Turning UPS off,
please wait...
8
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
990–3015E-001