9. Select UPS and press ENTER.
→ UPS Alarms
Power Dist Log
Switch Gear Admin
Environment Help
10. Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
11. Select Turn UPS Off and press ENTER.
→ Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
12. Select No, Don’t Notify and press ENTER.
Notify PowerChute ?
Cancel
Yes, Notify Servers
→ No, Don't Notify
13. Conrm by selecting YES, Turn UPS Off and
press ENTER.
Turn UPS Off Without
Server Notification?
>NO, ABORT
→ >YES, Turn UPS Off
14. Wait for the UPS to turn off.
Turning UPS off,
please wait....
15. Set the UPS SYSTEM ENABLE switch to the
OFF position.
16. Set the Q1 switch to the OFF position.
17. Set the Q5 breaker to the OFF position (if
applicable).
15
18. Set the DC DISCONNECT switch to the OFF
position on all XR Battery Enclosures and the
XR Battery Enclosures/PDU-XR
990–3015E-001
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
15