Replace a Battery
WARNING: Servicing of batteries should be performed or supervised by personnel
knowledgeable about batteries and the required precautions.
Caution: When replacing batteries, replace with same type and number of batteries or
battery packs.
Caution: Risk of explosion if battery is replaced by an incorrect type. Dispose of the
batteries according to the instructions.
Caution: Do not dispose of batteries in a re. The batteries may explode.
Caution: Do not open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
Caution: A battery can present a risk of electrical shock and high short circuit current. The
following precautions should be observed when working on batteries:
A. Remove watches, rings, or other metal objects
B. Use tools with insulated handles
C. Wear rubber gloves and boots
D. Do not lay tools or metal parts on top of batteries
E. Disconnect charging source prior to connecting or disconnecting battery terminals
Note: The batteries must only be replaced with model “High performance battery unit”.
Caution: Wait until the UPS system is ready to be powered up before installing battery
modules in the UPS. Installing the batteries more than 72 hours or 3 days before the UPS is
powered up can result in a deep discharge of the batteries and cause permanent damage.
28
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
990–3015E-001